If your Vaillant boiler is showing an F28 fault code, it tried to fire up and could not. The boiler makes several ignition attempts, fails to detect a flame and locks itself out for safety meaning no heating and no hot water until the cause is dealt with.
The good news is that F28 is one of the most common Vaillant faults and in many cases the cause sits outside the boiler itself. Here is what to check before you pick up the phone.
What does the F28 fault code actually mean?
F28 is an ignition lockout. On start-up the boiler opens its gas valve, fires the ignition electrodes and looks for a flame. If no flame is detected after repeated attempts, it stops trying and displays F28. It is a protective measure, not a sign your boiler is finished. The fault sits somewhere in the chain between your gas supply and the ignition components, and working out which end is the whole job.
Does F28 mean there is no gas?
Very often, yes. Before assuming the boiler is at fault, check whether gas is actually reaching it. Try another gas appliance such as your hob. If that will not light either, the problem is your supply, not the boiler. In London flats there are a few common culprits: a prepayment meter that has run out of credit, an emergency control valve that has been knocked or turned off, and in mansion blocks a communal gas supply that has been interrupted. In freezing weather the meter regulator outside can also ice up and starve the boiler of pressure.
Safe checks to try before calling an engineer
- Test another gas appliance. If the hob lights, gas is reaching the property and the fault is closer to the boiler.
- Check your meter and emergency valve. Top up a prepayment meter if needed and make sure the lever on the emergency control valve is fully open, in line with the pipe.
- Look at the condensate pipe in cold weather. If a white plastic pipe runs from the boiler to an outside drain, it can freeze and shut the boiler down. Thaw the frozen section with warm water, never boiling, then reset.
- Look at the flue terminal outside. Find where the flue exits the wall and check the outlet is clear. Leaves, nesting material, ice or a missing flue guard can all restrict it. Clear anything obvious from ground level only, and never poke anything into the flue itself.
- Check the pressure gauge. A cold system should sit between 1 and 1.5 bar. If it is below 1, top up using the filling loop under the boiler and try once more. Pressure is not usually the cause of F28, but a system running very low can stop the boiler completing its ignition sequence.
- Reset the boiler once. Press the reset button (the flame symbol with a line through it on most models) and let it retry. One reset is fine. Repeated resets against a genuine fault can make things worse, so if F28 returns, stop there.
F28 causes at a glance
| Cause | What to do |
|---|---|
| No gas reaching the property | Test another appliance, then contact your supplier |
| Prepayment meter out of credit | Top up and reset once |
| Frozen condensate pipe | Thaw with warm water, never boiling, then reset |
| Frozen meter regulator outside | Protect the meter from the cold, call your supplier if it persists |
| Blocked or obstructed flue terminal | Clear obvious debris from ground level, otherwise engineer |
| Low system pressure | Repressurise to 1 to 1.5 bar |
| Worn ignition electrodes or leads | Gas Safe engineer |
| Faulty gas valve or spark generator | Gas Safe engineer |
| Blocked burner jet | Gas Safe engineer |
F28, F29 or low pressure? Do not mix them up
These three get confused constantly. F28 means the boiler never lit. F75 points to a pump or pressure sensor issue. F29 means the flame lit and then went out while running. Low pressure shows as F22 or a pressure gauge below 1 bar, and topping up via the filling loop cures it. If your display clearly says F28, pressure is rarely the cause, so do not waste an evening bleeding radiators.
When to call a Gas Safe engineer
If the supply checks pass and a single reset does not clear it, the fault is likely inside the boiler: worn ignition electrodes, a faulty ignition lead or a gas valve problem. None of these are DIY jobs. Working on gas without being Gas Safe registered is illegal as well as dangerous, so this is the point to stop and call.
Plumus is a Vaillant accredited boiler repair company covering London 24/7. Our Gas Safe engineers carry the diagnostic kit to trace an F28 to its actual cause on the first visit, and repairs are backed by a 12 month guarantee. If the boiler has died at the worst possible moment, our emergency boiler repair guide covers what to do while you wait, or call us on 020 7126 7126 and we will confirm clear rates before anyone is dispatched.
Vaillant F28 FAQs
Can I fix an F28 fault myself?
You can safely check your gas supply, top up your meter, thaw a frozen condensate pipe and reset the boiler once. Anything involving the gas valve, electrodes or internal components legally requires a Gas Safe registered engineer.
Will resetting the boiler clear F28?
Only if the underlying cause has gone, for example after restoring gas supply or thawing the condensate pipe. If F28 comes back after one reset, something still needs fixing.
Why does F28 keep coming back?
A recurring F28 usually means worn ignition electrodes, a weak spark, a partially blocked gas supply or a gas valve on its way out. Electrodes fail in three ways: normal wear with age, vibration damage if the boiler has been rattling or humming, and moisture damage if there is an internal leak. That last one matters because replacing electrodes without fixing the leak simply repeats the fault, so a proper diagnosis comes first.
Is an F28 fault dangerous?
The lockout itself is the boiler keeping you safe. Never attempt to bypass it. If you smell gas at any point, call the National Gas Emergency line on 0800 111 999 straight away.